Model 1600A-N1P NEMA 1 Control Panel Operator’s Installation and Instruction Manual DETCON, Inc. 3200 Research Forest Dr., A-1
1600A-N1P 3.1 1600A Interface Board The 1600A Interface PCA is connected to a set of Terminal Blocks on the DIN Rail ( an
1600A-N1P 1600A Interface PCA (located on underside of 1600A-N1P Top Panel) LEDS: RST —This LED is normally off. It g
1600A-N1P 1M1L+0.00.10.20.30.41M0.00.10.20.30.40.50.60.70.50.60.72M2L+1.01.11.21.01.11.21.31.42M1.51.61.31.41.51.61.7°ML+1.
1600A-N1P 3.3 Installing the I/O Modules Normally, maximum of two (2) I/O modules may be factory installed on the main
1600A-N1P Figure 9 Model DA-4 and 4-20mA Gas Sensors RS-485 Modbus Gas Sensors Connect the five wires from the Modbus™ ga
1600A-N1P Relay Output Contact Modules There are four ‘Form C’ 5 Amp relay contacts in each Model RL4 module. These can b
1600A-N1P • Belden 9841 cable is recommended for a single cable providing serial communications only. Ground the cable
1600A-N1P 3.6 Setting Device Identification on the I/O Modules NOTE: If your Model 1600A controller has been configure
1600A-N1P 4.0 Setup 4.1 Program Menu Selections To enter the Program Menu touch Program Menu and see Passwords in Sect
1600A-N1P Figure 16 Channel Setup Figure 17 Individual Channel Setup Channel Activation: If the channel is active, t
1600A-N1P 1600A-N1P Instruction Manual ii Page intentionally blank
1600A-N1P 16 is 10 for ALARM 1, 20 for ALARM 2, 50 for ALARM 3. Touch the current value window, enter the new value on the
1600A-N1P Figure 19 DA4 / Analog input Activation Example: In this example, the 1600A is to be set up for two Model DA4
1600A-N1P Figure 20 Addressing Relay Modules Figure 21 Activating Relay Outputs Figure 22 Setting up Relay Outputs
1600A-N1P NOTE: This selection controls the output state for that relay regardless of how many alarm/fault conditions for
1600A-N1P Figure 24 Serial Setup screen Addressing Serial Sensors When connecting to a Detcon Model 600 or Model 700 Se
1600A-N1P Figure 25 Set-up 4-20mA Outputs For example, assume setting up two AO-4 modules. Make sure to set each AO-4
1600A-N1P Figure 26 Main Display Channels are displayed in groups of eight per screen, called ‘Zones’. The ‘Zones’ are
1600A-N1P Any time during the 60-minute countdown the user can return to normal operating mode by pressing the Cal Mode bu
1600A-N1P When using the 1600A as a Modbus slave, press the “SUPERVISORY MODBUS” key to adjust Modbus slave settings. See
1600A-N1P Figure 30 On-Screen Keyboard 5.5 Secondary Modbus™ Port Model 1600A controllers feature a Modbus™ compatible
1600A-N1P 1600A-N1P Instruction Manual iii Table of Contents 1.0 Introduction ...
1600A-N1P High Byte Bit 7 1 = Channel 16 Fault 0 = Channel 16 no Fault Bit 6 1 = Channel 15 Fault 0 = Chann
1600A-N1P Bit 4 1 = Channel 5 Alarm 2 0 = Channel 5 no Alarm 2 Bit 3 1 = Channel 4 Alarm 2 0 = Channel 4 n
1600A-N1P 5.6 Firmware Upgrade The 1600A-N1P is capable of firmware upgrades for both the PLC and touch screen device. U
1600A-N1P 6. Under "Device Type", select TP 177A 6”. 7. Under "Connection", select Serial (via USB-P
1600A-N1P 7.0 Warranty Detcon, Inc., as manufacturer, warrants under intended normal use each new Model 1600A-N1P contr
1600A-N1P Appendix A RS-485 System Integration Wiring RS-485 is a generic electrical specification only. It does not
1600A-N1P in industrial environments, shielded twisted pair is required. Wiring of 24 AWG is highly recommended, but 18 to
1600A-N1P Figure 34 Recommended RS-485 communications set-up Grounding Another problem that can occur with RS-485 is inc
1600A-N1P Figure 35 Unbalanced Data Bus The addition of 2 repeaters (Figure 36) can solve this problem. The
1600A-N1P Device Hook-Up Installation should begin by deciding where devices will be located and how the connections betwe
1600A-N1P Figure 1 Block Diagram ...
1600A-N1P In this case it is impossible to balance the data bus because there is no distinct beginning or end to the cable
1600A-N1P Appendix B Hexadecimal Table ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW2 ID# SW1 SW
1600A-N1P Appendix C Revision Log Revision Date Changes made 0.0 01/13/2009 None Initial release 0.1 08/14/2009 Ima
1600A-N1P Appendix D Drawings and Diagrams 1. 1600A-N1P Dimensional Overview 2. 1600A-N1P Unit Overview 3. 1600A-N1P
1600A-N1P 1600A-N1P Instruction Manual Rev. 0.1 Page 40 of 40
1600A-N1P 1600A-N1P Instruction Manual Rev. 0.1 Shipping Address: 3200 A-1 Research Fores
1600A-N1P 1600A-N1P Instruction Manual Rev. 0.1 Shipping Address: 3200 A-1 Research Fores
1600A-N1P 1.0 Introduction The Detcon Models 1600A-N1P is a “user-configurable” multi-channel alarm controller. The 1600
1600A-N1P 1600A-N1P Instruction Manual Rev. 0.1Shipping Address: 3200 A-1 Research Forest
1600A-N1P 1600A-N1P Instruction Manual Rev. 0.1Shipping Address: 3200 A-1 Research Forest
1600A-N1P 2.0 System Configuration 2.1 Hardware Configurations The Model 1600A-N1P is a “user configurable” alarm cont
1600A-N1P 3) Alarm level(s) for each gas channel 4) Tag Name for each channel 5) Assignment and set-up information for eac
1600A-N1P 3.0 Installation Securely mount the Model 1600A-N1P enclosure on a suitable panel opening. The recommended o
1600A-N1P Where applicable, connect the RS-485 wiring from remotely located I/O devices to the terminals located on the Ba