detcon inc.
Detcon MicroSafe
FP-524C Combustible Gas Sensor (0-100% LEL)
Operator’s Installation & Instruction Manual
August 12, 2010 • Document #2265 • Version 1.8
CAUTION:
Before operating the Model FP-524C sensor, read this manual thoroughly and verify that the
configuration of default factory settings are appropriate and correct for your application.
Page view 0
1 2 3 4 5 6 ... 20 21

Summary of Contents

Page 1 - Detcon MicroSafe

detcon inc.Detcon MicroSafe™FP-524C Combustible Gas Sensor (0-100% LEL)Operator’s Installation & Instruction ManualAugust 12, 2010 • Document #226

Page 2 - Table of Contents

There is a limit 0.5 ohm maximum resistance drop per wire over the seperation distance.AWG Maximum Seperation (feet)20 5018 7516 12514 175 Reference f

Page 3 - 3.0 DESCRIPTION

a) FP-524C “Fault” LED is off.b) A temporary upscale reading may occur as the sensor heats up. This upscale reading will clear to “0”% within 1-2 minu

Page 4 - Base Connector Board

labeled “PGM 1” and “PGM 2” allow for complete calibration and programming without removing the enclosurecover, thereby eliminating the need for area

Page 5 - Functional

Model FP-524C Combustible Gas Sensor PG.13MethylethylketoneCyclohexaneBenzeneHydrogen SulphideMethyl n-propylketoneToluene2,3-DimethylpentaneTriethy

Page 6 - 3.4 OPERATING SOFTWARE

3.7.2 Verification of Target Gas and Calibration Gas ConfigurationVerification of target gas and calibration gas configuration is obtained via intera

Page 7

b) Next, scroll to the “SET CAL FACTOR” listing and then hold the programming magnet over “PGM 1” for 3seconds. The menu item appears as “CAL FACTOR #

Page 8 - 3.5 INSTALLATION

b) If the calibration gas level setting is equal to your calibration span gas concentration, proceed to item “f”. Ifnot, adjust the calibration gas le

Page 9 - 3/4" NPT

3.9 STATUS OF PROGRAMMING, TARGET GAS, CALIBRATION GAS, CALIBRATION LEVEL, SENSOR LIFE, AND BRIDGE VOLTAGEThe programming menu has a programming stat

Page 10 - FP-524C-RS

Fail-Safe/Fault SupervisionModel FP-524C MicroSafe™ sensors are programmed for fail-safe operation. Any of the following fault conditionwill illuminat

Page 11 - Material Requirements

3. Check validity of cal gas via the expiration date and use pull tube if necessary.4. Check for obstructions through stainless steel sinter element (

Page 12 - Figure #6

Table of Contents3.0 Description3.1 Principle of Operation3.2 Application3.3 Specifications3.4 Operating Software3.5 Installation3.6 Start-up3.7 Targe

Page 13

3.13 SPARE PARTS LIST613-010000-000 Sensor rain shield613-120000-000 Sensor splash guard943-000006-132 Threaded Calibration Adapter 399-602016-000 LE

Page 14 - Material Requirements:

3.16 SOFTWARE FLOWModel FP-524C Combustible Gas Sensor PG.21NORMALOPERATIONCALIBRATIONPGM1 (3) PGM2 (3)PGM1 (M) PGM2 (M)PGM1 (3)INCDECPGM1 (3) PGM2

Page 15 - 3.8 CALIBRATION

3.0 DESCRIPTIONDetcon MicroSafe™ Model FP-524C, combustible gas sensors are non-intrusive “Smart” sensors designed to detectand monitor combustible g

Page 16 - Additional Notes

3.0.2 Microprocessor Control CircuitThe control circuit is microprocessor based and is packaged as a plug-in field replaceable module, facilitating e

Page 17 - 3.10 PROGRAM FEATURES

3.1 PRINCIPLE OF OPERATIONMethod of detection is by a controlled rate of diffusion/adsorption. Air and gas diffuse through a sintered stainlesssteel

Page 18 - 3.12 TROUBLE SHOOTING GUIDE

3.2 APPLICATIONModel FP-524C MicroSafe™ sensors are designed to detect and monitor combustible gas in ambient air in the range of0-100% LEL. Minimum

Page 19

a) Current Status02. Calibration Modea) Zerob) Span03. Program Menua) Program Statusb) Target gas selection (gas K factor)c) Calibration gas selection

Page 20 - Figure #7

3.5 INSTALLATIONOptimum performance of ambient air/gas sensor devices is directly relative to proper location and installation practice.3.5.1 Field

Page 21 - OFTWARE FLOW

Note: In all installations, the sensor element in SS housing points down relative to grade (Fig. 1). Improper sensororientation may result in false re