Detcon 1610A RACK User Manual

Browse online or download User Manual for Equipment Detcon 1610A RACK. Detcon 1610A RACK User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Detcon Model 1610A RACK
Panel Mount Control Enclosure
Operator's Instruction Manual
August 10, 2001 • Document #2471 • Version 1.0
1.0 INTRODUCTION
Detcon Model 1610A Rack consists of 3 major assemblies:
1. The NEMA 1 rack mount control enclosure.
2. The single channel digital control modules.
3. The remote mount gas sensor assemblies.
The NEMA 1 control enclosure is detailed in section 1.0 of the manual, the control modules in
section, 2.0 and applicable sensor assemblies in section 3.0.
1.1 DESCRIPTION
Detcon Model 1610A along with Model 10A digital control modules is designed to serve as a
host assembly for up to sixteen remote mount gas detection sensor assemblies. The control
enclosure is rated NEMA 1 suitable for installation in non-hazardous locations. The single chan-
nel modular design supports application flexibility wherein multiple function gas detection sys-
tems can be configured in any combination up to sixteen channels. All control modules are plug-
in front panel accessible for easy maintenance and repair.
Discreet output terminal strips located on the controller motherboard are provided for sensor
terminations, Form C dry contact alarm outputs (normally open, normally closed and common),
4-20 ma outputs for remote recording devices, alarm reset, and 24 VDC input.
Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located
on the controller mother board.
1.2 SPECIFICATIONS
ELECTRICAL CLASSIFICATION: NEMA 1
DIMENSIONS: 19"W, 5"H, 8.25"D
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
HIGH
LOW
FAULT
ALARM
RESET
HOUSTON, TEXAS
MODEL 10A
H
2
S MONITOR
ppm
L
O
C
K
detcon inc.
detcon inc.
Page view 0
1 2 3

Summary of Contents

Page 1 - Detcon Model 1610A RACK

Detcon Model 1610A RACKPanel Mount Control EnclosureOperator's Instruction ManualAugust 10, 2001 • Document #2471 • Version 1.01.0 INTRODUCTIOND

Page 2 - 1.7 WARRANTY

CAPACITY: 16 Single ChannelsPOWER: 24 VDC Input to Controller MotherboardALARM CONTACTS: Discreet Fault, Low, High, per Channel 2 Amp @ 30VDC/.6 Amp

Page 3

2.251918.255178.25MOUNTING HOLES - .25" DIA.PANEL CUT-OUT IS 17.5" x 4"#10-32 x .75 SCREW, #10 STAR WASHER AND #10 NUTFig. 1LOW NORMALL