INSTRUCTION MANUAL Model 700 Series Remote Sensor/Alarm Relay Module With Profibus DP Interface DETCON, Inc. 3200 Research
700 Profi-RAM NOTE: For any other required operational changes, the 700 Gas Sensor must be accessed directly. Software Flowchart dec
700 Profi-RAM In normal operation, the 4-20 mA current output from the Profi-RAM corresponds with the present gas concentration and
700 Profi-RAM mA Output Item appears as: “mA Output XX.XX” Input Voltage Supply Item appears as: “Voltage XX.XXVDC” Sensor Tempera
700 Profi-RAM The user can then choose to either: 1) move to another menu item by executing a momentary hold, or 2) return to Norma
700 Profi-RAM The display will scroll “Set Ascending” and show “Yes” or “No”. Momentarily swipe PGM1 to select the desired choice (y
700 Profi-RAM 3.6 PDP Diagnostics PDP Diagnostics displays the current status of the AnyBus Profibus connection to the network. T
700 Profi-RAM The PROFIBUS-DP Protocol is implemented using the HMS Industrial Networks, Inc. AnyBus-IC for PROFIBUS. The Profibus N
700 Profi-RAM Word 7: Sensor Temperature. Minimum value: -40 Maximum value: 75 Word 8: Range Divisor. This setting is determi
700 Profi-RAM Profibus RAM I.M. Rev. 0.3 Page 14 of 14 Enclosure Classification Nema 7 and Nema 4X
700 Profi-RAM 700 Profi-RAM 0.3 ii This page left intentionally blank Shipping Address:
700 Profi-RAM 700 Profi-RAM iii Table of Contents 1. Introduction ...
700 Profi-RAM 700 Profi-RAM 0.3 iv This page left intentionally blank Shipping Address: 3200 A-1 Resear
700 Profi-RAM 1. Introduction 1.1 Description The Model 700 Remote Sensor/Alarm Relay Module with Profibus Interface (known as th
700 Profi-RAM 5.5" 3.675"5.25"Ø0.2650 X2Mounting Holes4.95"Model 700Model 700Three - 34"NPT FittingsExplosio
700 Profi-RAM Profi-RAM ElectronicsPackageExternal WiringInterconnectWiringConnectorsInput PortThe ElectronicsPackage setson thesta
700 Profi-RAM NOTE: If the 700 sensor and Profi-RAM are directly connected, it is not necessary to install/use the transient protect
700 Profi-RAM NOTE 3: The same recommended cables should be used for the connection between the master control device and the Profi